Fire safety compliance in Queensland is not one obligation, it is six, and they sit in different parts of the same regulation. Most businesses do the first one, some do the second, and the rest come up for the first time when something goes wrong or the building changes hands.
The rules live in the Building Fire Safety Regulation 2008, made under the Fire Services Act. They apply to the occupier of the building, and they apply whether the building is owned or leased. Here is the whole list.
The six obligations, in short
- Maintain the equipment to the standard, and keep the records.
- Have a fire and evacuation plan, reviewed at least once a year.
- Display evacuation signs and diagrams on the evacuation routes.
- Instruct your workers, within 2 days of starting and at least yearly after that.
- Run a practice evacuation at least once a year.
- Prepare an occupier's statement each year and give a copy to the commissioner within 10 business days.
1. Maintain the equipment, and keep the records
Every prescribed fire safety installation in the building has to be inspected, tested and maintained at the intervals set out in the Queensland Development Code part MP 6.1, which in practice means the routine service schedules in AS 1851-2012 and the standard specific to each installation.
What that covers in a typical commercial building:
- Portable fire extinguishers, six-monthly, with a five-yearly pressure test.
- Fire blankets, on the same visit as the extinguishers.
- Emergency and exit lighting, including a six-monthly 90-minute discharge test.
- Fire hose reels and fire hydrants, where fitted.
- Fire detection and alarm systems, including smoke alarms and the panel.
- Fire and smoke doors, and any other passive installation the building was approved with.
The records matter as much as the work. You need to be able to show what was inspected, when, by whom, what was found and what was done, and the records have to be available at the building.
2. Have a fire and evacuation plan
The occupier of a building must have a written fire and evacuation plan for it, and under section 28 that plan has to be reviewed at intervals of not more than one year. A plan written for a business that has since knocked out a wall, taken on twice the staff or changed what it stores is not a plan, it is a document.
The plan sets out what people do when the alarm goes: who is responsible for what, how the building is cleared, where people assemble, and how anyone who needs help is accounted for.
3. Display evacuation signs and diagrams
Signs and diagrams have to be located along each evacuation route, positioned for the number and location of the exits. A diagram has to show, among other things, the point in the building where that diagram is displayed and each exit from the building. A generic floor plan with no you-are-here marker does not satisfy it. There is more detail in our guide to evacuation diagrams.
4. Instruct your workers
This is the one that gets missed, because it is not about equipment and nobody invoices you for it. Under section 35, general fire and evacuation instructions have to be given to workers at intervals of not more than one year, and a new worker has to be instructed no later than 2 days after they start.
If your plan gives particular people a first-response role, using an extinguisher or a hose reel before the brigade arrives, section 36 adds a second layer: those people are instructed no later than one month after starting, and at intervals of not more than two years.
Two days is short. In a business with normal turnover it means fire instruction has to be part of the induction, not something that happens when the trainer is next on site.
Staff training is done in your building, with your equipment, so people learn the layout they will actually be evacuating. It covers the general instruction and the first-response instruction, and you get the attendance record for your file. See how the training works.
5. Run a practice evacuation
Under sections 43 and 44, a practice evacuation has to be carried out at intervals of not more than one year, for budget accommodation buildings and for other buildings alike. Keep a record of it with the plan: when it was run, who took part, how it went and anything that needs fixing as a result.
That last part is the useful bit. Most practice evacuations turn up something real, a door that sticks, an assembly point that puts people in a driveway, a section of the building that nobody thought to sweep.
6. Prepare an occupier's statement each year
Once a year the occupier prepares a statement confirming the building's prescribed fire safety installations have been maintained as required, and under section 55A gives a copy to the commissioner within 10 business days of when the statement was required to be prepared. A copy stays with your maintenance records.
The statement is a summary of everything above. If the servicing is on schedule and the records are in order, it is a form. If it is not, it is a problem, because you are being asked to certify something you cannot evidence. We cover it properly in the occupier's statement guide.
How this usually goes wrong
Almost never through indifference. It goes wrong in three ways, and all three are ordinary:
- The building changes hands or contractors. The service history goes with the previous contractor and nobody rebuilds the register, so the next twelve months run blind.
- The person who tracked it leaves. Fire compliance lived in one manager's calendar, and the calendar left with them.
- The equipment is serviced but nothing else is. The extinguishers are perfect and there has been no practice evacuation in four years, because equipment has a contractor and the rest of it does not.
Where to start if you are behind
Start with an audit rather than with a purchase. You need to know what installations the building has, what condition they are in, what records exist and which of the six obligations above are currently unmet. That is a morning's work in most buildings and it turns an open-ended worry into a list.
From there it is ordinary: put the equipment on a schedule, review the plan, get the diagrams right, book the instruction and the practice, and the statement takes care of itself.