Under the Building Fire Safety Regulation 2008, the occupier of a Queensland building has to have a written fire and evacuation plan for it, has to display evacuation signs and diagrams along the evacuation routes, has to instruct workers about both, and has to run a practice evacuation at least once a year. Four connected obligations, and the diagram on the wall is only the visible one.
The plan
The fire and evacuation plan is the document that sets out what actually happens when the alarm goes. Who is responsible for what. How the building is cleared and by whom. Where people assemble and how they are accounted for. What happens for anyone who cannot use the stairs or cannot hear the alarm. How the brigade is met and briefed when it arrives.
Under section 28, the plan is reviewed at intervals of not more than one year. It should also be reviewed any time the building or the way it is used changes, because that is when a plan silently stops being true: a new mezzanine, a doorway blocked off in a refit, a tenancy split in two, a night shift added.
The diagram
Evacuation signs and diagrams have to be located along each evacuation route, positioned with regard to the number and location of exits. The regulation is specific about what a diagram has to show, including the place in the building where that diagram is displayed and each exit of the building.
That first requirement is the one most often missed. A diagram is not a floor plan of the premises, it is a floor plan oriented to where the reader is standing, with a you-are-here marker. The same artwork cannot be printed six times and hung on six walls, because on five of them it is wrong.
What goes on a compliant diagram
- The you-are-here point, matching where the diagram actually hangs.
- Every exit from the building, and the evacuation route from this point to them.
- The assembly area, so people know where they are heading once outside.
- The fire safety equipment nearby: extinguishers, blankets, hose reels, alarm call points.
- The date it was validated, so a reviewer can see it is current.
- Correct orientation, drawn the way the reader is facing rather than the way the architect drew it.
Where the diagrams go
On the evacuation routes, where someone leaving would pass them: lift lobbies, stair landings, main corridors, the entrance to each tenancy, near reception. Fixed to the wall at a readable height, not laminated and cable-tied to a shelf. The test is straightforward. If a visitor who has never been in the building before stops at that spot, can they work out where to go?
Instructing people, and the practice evacuation
A diagram nobody has looked at does not evacuate a building. Under section 35, general fire and evacuation instructions have to be given to workers at intervals of not more than one year, and to a new worker no later than 2 days after they start. If particular staff have a first-response role under the plan, section 36 requires them to be instructed within one month of starting and at least every two years.
Then the practice. Under sections 43 and 44, a practice evacuation is carried out at intervals of not more than one year, and a record of it is kept with the plan: when it was run, who took part, and what needs to be fixed as a result.
The record of what needs fixing is the part with real value. In our experience a first practice evacuation in a building that has not had one always finds something: a fire door wedged open on a hot day, an assembly point in a delivery driveway, a back area of the building nobody was assigned to sweep, or a wing where the alarm cannot actually be heard over the plant.
We prepare the plan, draw and install diagrams that are oriented correctly for each location, run the staff instruction on your floor and run the practice evacuation with you. You end up with a set of records that matches the building. See evacuation plans.
Who this applies to
Broadly, occupiers of Queensland buildings other than ordinary houses and townhouses. The detail changes with the building: budget accommodation carries extra requirements, and a high-occupancy building has more to satisfy than a small tenancy. If you occupy commercial premises, assume it applies to you and work from there.
The honest summary
The plan, the diagrams, the instruction and the practice are the four cheapest obligations in the whole regulation and the four most often left undone, because none of them arrive as an invoice from a contractor. They are also the four that decide what actually happens in the ninety seconds after an alarm, which is a better reason to do them than the regulation is.