QBCC Licence 1213114 Warwick base, SW & SE QLD Mon to Fri, 7am to 4pm
(07) 4661 1116
Total Fire Protection ServiceWarwick QLD
A commercial warehouse interior of the kind covered by an annual occupier's statement

Compliance

The annual occupier's statement: what it is and how not to get caught out

Once a year you sign a document saying the building's fire safety installations have been maintained properly. It takes ten minutes if the year went well, and it is a very bad ten minutes if it did not.

The occupier's statement is the annual full stop on everything else. Each year the occupier of a Queensland building prepares a statement confirming that the building's prescribed fire safety installations have been inspected, tested and maintained as required, and under section 55A of the Building Fire Safety Regulation 2008 gives a copy to the commissioner within 10 business days of when the statement was required to be prepared. A copy is kept with your maintenance records.

It is short. It is also a certification, which is the part worth taking seriously: you are stating, on the record, that the year's maintenance happened.

The facts

  • Who: the occupier of the building. In a leased commercial premises that is usually the tenant.
  • How often: every 12 months.
  • What it covers: every prescribed fire safety installation in the building.
  • The deadline: a copy to the commissioner within 10 business days of when the statement was required to be prepared.
  • Where the form comes from: the approved form published by the Queensland Fire Department, at fire.qld.gov.au.
  • Keep a copy with the building's maintenance records.

What counts as a prescribed fire safety installation

Whatever the building was approved with and relies on. In a typical commercial building that is portable fire extinguishers and fire blankets, emergency and exit lighting, fire hose reels and hydrants, fire detection and alarm systems including smoke alarms and the panel, and the passive installations such as fire and smoke doors.

The statement covers all of it at once, which is why it is the item that exposes a gap. Businesses that have a contractor for extinguishers and nothing for emergency lighting find out at statement time, because they are being asked to certify both.

The three ways it goes wrong

  1. Nobody knows it exists. Common in small tenancies and in businesses that have never had an inspection. The equipment might be perfectly maintained and the statement has still never been prepared.
  2. The records do not cover the whole building. Extinguishers serviced on schedule, emergency lighting untested for three years. You cannot honestly certify the second one.
  3. The anniversary drifts. The statement is annual, and the 10 business day window runs from when it was required to be prepared, not from when someone remembered. If nobody owns the date, it slips a month a year until it is nine months late.

What to do if you are behind

Do not sign it. A statement certifying maintenance that did not happen is worse than a late statement, and it is your name on it.

The order of work is:

  • Find out what the building actually has. A walk-through that lists every installation, its condition and its last recorded service. If there are no records, the register is built from scratch.
  • Bring the servicing current. Anything overdue is done, anything failed is repaired or replaced, and everything goes onto a schedule with real dates.
  • Fix the record. One asset register for the building, with the maintenance history attached and kept at the premises.
  • Then prepare the statement, on this year's anniversary, from records that support it.

None of that is dramatic. In most buildings it is one audit visit, one catch-up service and a schedule, and from then on the statement is a formality.

We keep the schedule so the statement is never a scramble

Buildings on a maintenance plan with us get serviced when the interval is due rather than when someone remembers, with the records issued the same week. When the anniversary comes around, the evidence is already there. See how the plans work or ask for a quote.

Owner or tenant?

The duty sits with the occupier. In a leased commercial building that is normally the tenant, even where the equipment belongs to the landlord and the lease passes the maintenance cost back to them. The lease decides who pays. The regulation decides who is responsible.

If you are a tenant and the landlord's contractor maintains the base building systems, you still need the records for those systems to prepare your statement. Ask for them well before the anniversary, not in the 10 business day window.

The short version

Annual, covers everything, 10 business days to lodge a copy, keep one with your records, and only sign it if the year behind it holds up. Get the servicing on a schedule and it is the easiest obligation you have. Leave the servicing to chance and it is the one that finds you out.

Written from the workshop at 96-98 Grafton Street, Warwick. General information only, not a substitute for advice on your own building. For a straight answer on your premises, give us a call.

All fire safety advice

Keep reading

More from the workshop

Common questions

Questions we
get asked

If yours is not answered here, ask us on the phone. We would rather sort it out before you book than after.

What is an annual occupier's statement in Queensland?

A statement prepared each year by the occupier of a building confirming that the building's prescribed fire safety installations have been inspected, tested and maintained as required. Under section 55A of the Building Fire Safety Regulation 2008, a copy must be given to the commissioner within 10 business days of when the statement was required to be prepared, and a copy kept with the maintenance records.

Who has to prepare the occupier's statement, the owner or the tenant?

The duty sits with the occupier of the building, which in a leased commercial premises is usually the tenant, even where the landlord owns the equipment or pays for its maintenance. The lease decides who pays; the regulation decides who is responsible.

What happens if you do not lodge an occupier's statement?

Failing to prepare the statement, failing to keep a copy with the maintenance records and failing to give a copy to the commissioner within 10 business days are each offences under the Building Fire Safety Regulation 2008. The more immediate problem is that a missing statement usually points to maintenance that has not been done.

What does the occupier's statement cover?

Every prescribed fire safety installation in the building. In a typical commercial building that means fire extinguishers and blankets, emergency and exit lighting, hose reels and hydrants, detection and alarm systems including smoke alarms and the panel, and passive installations such as fire and smoke doors.

Statement due and the records are not there?

We will audit the building, bring the servicing current and set the schedule, so next year's statement writes itself.