An exit sign that is lit is not the same as an exit sign that works. Mains power is what keeps it glowing on an ordinary day. What matters is the battery behind it, and whether that battery can still run the light for the full 90 minutes after the power drops out, which is the situation the sign exists for.
That is why the test is a discharge test rather than a look. Under AS/NZS 2293.2, emergency and exit lighting in a building is discharge tested at intervals not exceeding six months, and the results are recorded in the system logbook.
What the 90-minute discharge test involves
The mains supply to the emergency lighting circuits is isolated, which simulates a power failure. Every emergency luminaire and exit sign in the building then has to illuminate on its own battery and stay usefully lit for the full rated duration, normally 90 minutes.
At the end of the period each fitting is checked again. A light that came on and then faded out at forty minutes has failed just as surely as one that never lit at all, and the fitting or its battery is repaired or replaced. Then the power is restored and the system is left to recharge.
The other checks happen at the same visit: that each fitting is clean and undamaged, that the diffuser has not yellowed to the point of dimming the output, that the exit sign is the right pictogram and is visible from the direction of approach, and that nothing has been built, stacked or hung in front of it.
The intervals
- Six months. Full 90-minute discharge test of every emergency luminaire and exit sign, recorded in the logbook.
- Every visit. Physical condition, cleanliness, correct signage and clear sightlines.
- On failure. Repair or replace, then retest. A failed fitting is not a note for next time.
- Recharge. Batteries need time to come back up after a full discharge, so the system is not fully protected again for several hours.
Why lights fail the test
Almost always the battery. Emergency lighting batteries are consumables. They are trickle charged continuously, they sit in ceiling spaces that get hot, and out here they get very hot. Three to four years is a normal working life and heat shortens it. A building that has never had a battery replaced has an emergency lighting system in name only.
The rest of the failures are mundane. A fitting that was isolated during a refit and never switched back on. A circuit that was rewired so half the floor no longer sits on the emergency supply. A sign painted over. A sign hidden behind new racking, which is the warehouse classic.
The logbook is part of the installation
The system has a logbook, and the logbook is not optional. It records each test, the date, who performed it, the result for each fitting and what was done about failures. When someone asks whether the emergency lighting is compliant, the logbook is the answer, not the lights.
If you have taken over a building and there is no logbook, the practical fix is to start one with a full test and a fresh schedule of every fitting in the building. That schedule then becomes the reference for every visit after it.
Isolating the emergency circuits for 90 minutes is disruptive in some buildings and impossible in others during trading. We schedule around how the building actually runs. See the exit lighting service.
What it costs to leave it
Emergency lighting is a prescribed fire safety installation, so it sits inside the same compliance frame as the rest of the building. Its maintenance is part of what your annual occupier's statement covers, which means signing that statement with an untested system is signing something you cannot evidence.
The real cost is not the audit finding though. A dark stairwell in a building full of smoke is a different building from a lit one, and the sign at the end of the corridor is the only thing telling people which way to go.
Common questions we get on site
Do the lights have to be tested by an electrician?
The work has to be done by a competent person and recorded properly. In practice it means someone who can isolate the circuits safely, test to the standard, replace failed fittings and batteries, and leave you with a logbook entry that stands up.
Can a self-testing system replace the visit?
Automatic test systems do the discharge cycle for you and flag failures, which is a genuine improvement in a large building. They do not remove the need for the physical inspection or for the records, and something still has to act on what the system reports.
Our building is small. Does it still apply?
If the building was approved with emergency lighting or exit signs fitted, they are a prescribed installation and they have to be maintained. Size changes how long the test takes, not whether it is required.
Written from the workshop at 96-98 Grafton Street, Warwick. General information only, not a substitute for advice on your own building. For a straight answer on your premises, give us a call.
All fire safety advice